Subpanel Sizing & Feeder Wire Calculator

Determine subpanel electrical feeder wire gauge (copper vs aluminum), 2-pole main breaker size, conduit dimensions, and detached building grounding requirements.

Calculated Results

Recommended Feeder Cable Size
#4 AWG Aluminum (4-Wire)
Two hots, one neutral, one ground (4-wire feeder)
Main Panel Breaker Required
60 A (2-Pole 240V)
Double-pole feeder breaker
Minimum PVC Conduit Size
1-1/4 Inch Schedule 40
NEC 40% conduit fill rule
Grounding Requirements
Isolated Neutral Bar
Do NOT bond neutral to ground
Voltage Drop at 75 ft
1.4% (3.4 V)
Well below 3% NEC limit
Advertisement
In-Content Ad Banner (728x90)

Frequently Asked Questions

Why must subpanels have a separate neutral and ground wire (4-wire system)?

In a main electrical service panel, neutral and ground are bonded together. In all subpanels, the National Electrical Code (NEC 250.32) requires that neutral and equipment grounding conductors remain completely isolated. The neutral bonding screw/strap must be removed so normal return current does not energize metal conduit or panel cabinets.

What wire size is needed for a 60A and 100A subpanel?

For 60A: #6 AWG copper (or #4 AWG aluminum). For 100A: #3 AWG copper (or #1 AWG / #2 AWG aluminum). For detached structures, Mobile Home Feeder (MHF) quadruple aluminum is the most economical code-compliant wire.

Do detached garage subpanels require new ground rods?

Yes. NEC Article 250.32 mandates that any detached building served by a feeder must have its own grounding electrode system (typically two 8-foot copper ground rods driven into the earth spaced at least 6 feet apart).

What conduit size is required for running subpanel feeder wires?

Per NEC Chapter 9 conduit fill rules (40% maximum fill for 3+ conductors): #6 to #4 AWG wire requires a minimum 1-inch to 1-1/4-inch Schedule 40 or 80 PVC conduit; #1 or 1/0 AWG wire for 100A requires 1-1/2-inch or 2-inch conduit.