Conduit Fill & Wire Capacity Calculator (NEC)

Calculate electrical conduit fill percentage (40% maximum rule), wire capacity, and ampacity derating factors for EMT, PVC, and RMC with THHN wires.

Calculated Results

Conduit Fill Percentage
22.6% (PASSED)
Meets NEC 40% maximum allowable fill limit
Max Allowable Fill (40%)
0.213 Sq In
For 3 or more conductors
Actual Total Wire Area
0.120 Sq In
9 wires × 0.0133 sq in
Max Wires of this Gauge
16 Wires Max
Before exceeding 40% limit
Ampacity Derating Factor
70% (7 to 9 wires)
NEC Table 310.15(C)(1) heat adjustment
Advertisement
In-Content Ad Banner (728x90)

Frequently Asked Questions

What are the NEC conduit fill percentage limits?

Per NEC Chapter 9, Table 1: 1 conductor: maximum 53% fill; 2 conductors: maximum 31% fill (to prevent jamming during pulling); 3 or more conductors: maximum 40% fill.

Why does the NEC restrict conduit fill to 40%?

Restricting fill to 40% prevents severe mechanical damage to wire insulation during pulling through elbows and ensures adequate air circulation space to dissipate heat generated by electrical current.

What is wire ampacity derating for conduit?

When more than 3 current-carrying conductors share the same conduit or raceway, heat accumulates. The NEC requires derating allowable ampacity: 4 to 6 wires: 80% capacity; 7 to 9 wires: 70% capacity; 10 to 20 wires: 50% capacity.

Why does Schedule 80 PVC hold fewer wires than EMT?

Schedule 80 PVC has much thicker plastic walls to withstand physical impact damage. This reduces the interior cross-sectional area compared to thin-wall EMT or Schedule 40 PVC.